Exam Title: HCIP-Data Center Facility Deployment V2.0

Last update: Nov 27 ,2025
Question 1

Which of the following statements about the functions of the AC PDB is false?

  • A. Supplies power to air conditioners.
  • B. Supplies power to fans.
  • C. Supplies power to the extinguishant control panel.
  • D. Supplies power to sockets in the modules.
Answer:

D

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 2

Which of the following position is recommended for installing the smart ETH gateway?

  • A. Control skylight
  • B. Inside a network cabinet
  • C. At the inner side of a door header
  • D. At the side of a cable trough
Answer:

B

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 3

When installing a water-cooled module, what is the minimum distance between the module and the
wall?

  • A. 300 mm
  • B. 400 mm
  • C. 500 mm
  • D. 600 mm
Answer:

D

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 4

On the ECC800-Pro WebUI, which of the following is the first-level menu of the NMS Application?

  • A. System Settings
  • B. Maintenance
  • C. Home
  • D. Monitoring
Answer:

A

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 5

The UPS5000-E-200K works in normal mode. If two ECMs are faulty, how does the UPS work?

  • A. The UPS has no output.
  • B. The UPS transfers to bypass mode.
  • C. The LCD is off, but the UPS still works in normal mode.
  • D. The UPS switches to battery mode.
Answer:

B

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 6

If the battery charge current limit coefficient of the UPS5000-E is set to 0.1C10, which of the
following statements about this parameter is true?

  • A. The maximum batten/ charge current is 0.1C10.
  • B. The batten/ charge current is always 0.1C10.
  • C. The battery float charge current is 0.1C10.
  • D. The maximum battery charge current is 0.1C10.
Answer:

A

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 7

When the outdoor unit of a Huawei air-cooled air conditioner is installed horizontally, what is the
minimum distance between the outdoor unit and the wall or obstacle?

  • A. 100 mm
  • B. 200 mm
  • C. 300 mm
  • D. 600 mm
Answer:

C

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 8

Which of the following requires a cooling tower or drycooler?

  • A. Direct ventilation air conditioning system.
  • B. DX air cooled air conditioner.
  • C. CW air cooled air conditioner.
  • D. DX water cooled air conditioner.
Answer:

D

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 9

Which of the following components does not support wireless networking?

  • A. Access actuator
  • B. AC actuator
  • C. Aisle light
  • D. Skylight actuator
Answer:

D

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments
Question 10

Which of the following menus can be used by engineers to manually add devices on the NetEco?

  • A. Data center planning
  • B. Report management
  • C. Alarm management
  • D. System management
Answer:

D

vote your answer:
A
B
C
D
A 0 B 0 C 0 D 0
Comments